Frost Protection

Wattplot v3.3 adds a frost-prevention feature that drives either a resistive heating mat or a USB grow light (or both) when soil and/or canopy air temperature drops below a user-set threshold.

The feature is opt-in: by default the Frost Mode select is set to Off and nothing happens. The user picks what to wire up and how to control it.

What it does

Every 60 seconds the frost_tick interval in wattplot.yaml:

  1. Reads Soil Temperature and Canopy Air Temperature (DS18B20 1-Wire sensors).
  2. Reads Battery SOC (LiFePO4 voltage lookup).
  3. Checks Frost Mode:
    • Off → both switches forced off, no automation.
    • Heater → only the heater relay responds to the temp logic.
    • Grow Light → only the grow light relay responds.
    • Both → both respond, independently.
  4. For each enabled output, applies:

    State Condition
    ON soil < soil_threshold OR canopy < canopy_threshold
    OFF soil > warm_above AND canopy > warm_above
    hold anything in the deadband (between threshold and warm_above)
  5. Applies a watchdog that force-off after frost_max_runtime_min (default 30 min) — catches a stuck relay before it can drain the pack overnight.
  6. Applies a battery floor: if SOC drops below frost_min_battery_soc (default 50%), force off. We’d rather lose a few plants than brick the LiFePO4 pack.
  7. Applies a sensor-error latch: if BOTH temperatures are NaN at the same tick, the tick disables both switches and reports Sensor error in the Frost State text sensor. The latch clears on the next tick that has at least one valid reading.

Hysteresis

The two thresholds and the warm_above parameter form a deadband:

        soil/canopy temp
   ^
   |   warm (off)
   |   ─────────────── warm_above (e.g. 6°C)
   |   ░░░░░░░░░░░░░░░░ deadband
   |   ──────────────── threshold (e.g. 4°C)
   |   cold (on)
   v

The relay turns ON when either sensor drops below its threshold. It turns OFF only when both sensors are above warm_above. This deadband prevents relay chatter at the threshold edge — without it, a sensor reading right at 4.000°C would oscillate every tick.

The deadband is asymmetric (4°C threshold, 6°C warm_above) so the load has hysteresis even on slow temperature trends.

Forecast preheat (NWS)

The nws_poll script runs every 15 min and pulls the NWS forecast for the wattplot’s gridpoint (Phoenix PSR/153,87). The frost tick consumes the forecast and engages the load before the sensors say cold — saves the heater’s first hour of warmup.

How it works

Every 60 s, the tick computes:

forecast_preheat = (
    NWS poll is fresh (< 4 h old)
    AND forecast_min_tonight < frost_forecast_threshold_c
)

If forecast_preheat is true:

Why the hysteresis arm is suppressed

A typical scenario: it’s 6 pm, the soil is 7°C (above warm_above = 6°C), and the forecast says 0°C tonight. Without the forecast arm, the hysteresis would release the heater (both temps > 6°C). Then when temps drop to 4°C at 1 am, the sensor arm engages, but the heater takes 30+ minutes to warm up the bed. Plants are already cold by then.

With the forecast arm, the heater stays on from 6 pm through morning, holding the bed at a warmer temperature. The preheat is the entire point of consuming the forecast.

Stale-forecast handling

NWS updates forecasts roughly every 6 hours. A poll that’s older than 4 hours is considered stale and ignored. This prevents the preheat from running on day-old data (the forecast was for yesterday’s overnight, not tonight’s).

A failing NWS poll leaves the previous forecast value intact (rather than clearing it). Better to act on stale data than on no data.

Sensors broken? Forecast still works.

If both DS18B20s return NaN, the sensor-error path normally force-off. But if the forecast is preheating, the tick drives the load on the forecast alone. The weather outside doesn’t care about our wiring — and the user is more likely to be troubleshooting the sensors in the morning than in a cold snap, so the forecast keeps things running until they can fix the sensor.

Disable forecast preheat

Set Frost Forecast Threshold (°C) to -100. The comparison forecast < threshold is then always false, and the preheat arm never fires. The tick falls back to sensor-only logic.

Two watchdog limits

The frost protection has TWO watchdog limits, one per arm:

Knob Default Used when
Frost Max Runtime (min) 30 Sensor arm (sensors say cold)
Frost Preheat Max Runtime (min) 480 Forecast arm (NWS says cold)

The tick picks the right one based on which arm is keeping the load on:

int effective_max_runtime_ms = forecast_preheat
    ? preheat_max_runtime_ms    // 8h default
    : max_runtime_ms;            // 30 min default

Why two limits?

The sensor arm limit (30 min) is the safety net for a stuck relay during an active cold snap. A 30 W heater at 12 V pulls 2.5 A; a 10 Ah LiFePO4 pack dies in 4 hours if the relay is stuck. The 30 min cap means a stuck relay costs at most 0.8 Ah before the watchdog trips — leaves plenty of margin for a real fault.

The forecast arm limit (8 h) is for overnight preheat. The whole point of preheat is to run the heater for the whole cold night, not for 30 minutes. With a 30 min cap, the preheat would trip at 6:30 am and the bed would freeze by 7. With an 8 h cap, the preheat can run from 6 pm to 2 am — when the sun starts to warm the bed again.

When the limit flips

Power budget at the limits

For the wattplot mini (10 W panel, 12 V 10 Ah LiFePO4 pack):

Load Power 8h runtime Pack drain
30 W heating mat 30 W 240 Wh 200% of pack — pack dies
10 W USB grow light 10 W 80 Wh 67% of pack — pack survives
5 W LED panel 5 W 40 Wh 33% of pack — pack comfortable

A 30 W heater at the default 8 h preheat will deplete the battery. For overnight preheat, use a 5-10 W load (USB grow light or low-power LED panel), not a 30 W mat. The battery floor (Frost Min Battery SOC (%), default 50%) trips first for a heater that draws more than the pack can supply overnight.

For the full-size build (larger battery, 620 W panel), the battery floor and the watchdog are both fine. The 30 W mat can run a full night if the pack is sized accordingly.

Hardware

The firmware does NOT include the relay or the load. The ESP32 just drives a logic-level GPIO; you wire your own relay.

Pin assignments

GPIO Output ID Switch Use
39 frost_heater_out Frost Heater Heater relay (default)
40 frost_grow_light_out Frost Grow Light Grow light relay

Both are pulled LOW by default. Drive HIGH to energize the load through your external relay.

Wiring the heater (12V resistive mat)

A 30W heating mat at 12V draws ~2.5A. The wattplot’s Sunapex 10A MPPT has plenty of headroom, but the relay MUST switch the 12V load, not the GPIO. Recommended:

The heating mat goes in the bed on top of the soil, covered by mulch. The soil-temperature sensor sits in the soil at 5 cm depth within ~30 cm of the mat so the control loop is closed on the temperature the mat is actually warming.

Wiring the USB grow light (5V)

The wattplot’s PCB already carries 5V (the MP1584EN buck output). Tap that rail through a low-side N-MOSFET to a USB-A jack, or use a 5V relay module. Most USB grow light panels draw 0.5-2A at 5V (2.5-10W) and provide a few degrees of radiant heat.

For a 12V grow light panel (more common, brighter, more heat): drive a 12V relay from GPIO40 the same way as the heater.

Power budget

Load Voltage Current Wattage
30W heating mat 12V 2.5A 30W
10W USB grow light 5V 2A 10W
Both (worst case) mixed mixed 40W

At 40W the LiFePO4 pack (10Ah × 12V = 120Wh) lasts ~3 hours. The default 30-min watchdog will trip first — that’s the point. A cold snap that lasts 4 hours will see two watchdog cycles.

Sensors required

If only one of the two sensors is wired, the tick uses whichever one is valid. The behavior is symmetric — the same NaN guard that handles a wiring fault also handles a single-sensor build.

Tunable parameters

All five are number: entities in Home Assistant. The defaults are tuned for Phoenix, AZ (USDA zone 9b, design temp 25°F / -4°C). Tighter for spring transplants, looser for mature fall plants.

Parameter Default Range What it controls
Frost Soil Threshold (°C) 4.0 -5 to 10 Below this → turn ON
Frost Canopy Threshold (°C) 2.0 -5 to 10 Below this → turn ON
Frost Warm-Above (°C) 6.0 0 to 15 Above this (both) → turn OFF
Frost Max Runtime (min) 30 5 to 240 Watchdog (sensor arm)
Frost Preheat Max Runtime (min) 480 30 to 1440 Watchdog (forecast arm)
Frost Min Battery SOC (%) 50 10 to 80 Force off below this
Frost Forecast Threshold (°C) 2.0 -20 to 10 NWS forecast preheat trigger

Frost State text sensor

Frost State is a 5-second-updated text sensor that surfaces the most recent decision. Values:

Value Meaning
Off Frost Mode is Off, automation is disabled
Standby Mode is enabled but temps are above threshold
Heater Heater relay is energized
Grow Light Grow light relay is energized
Both Both relays are energized
Battery low SOC below floor; both forced off
Sensor error Both temps NaN; latched until a sensor recovers

Logging

The frost tick logs every state change at INFO level under the frost tag. Watchdog trips log at WARN. Sensor errors log at ERROR (once per latch, not once per tick). To see these in the HA log, make sure the mqtt.log_topic: "wattplot/log" config is in place — the local log subscriber at tools/log_subscriber.py writes them to logs/wattplot.log.

Manual control

Set Frost Mode to Off and the two switches (Frost Heater, Frost Grow Light) become purely manual — they can be toggled from HA and the tick will leave them alone. Useful for:

Limitations

Tests

firmware/tests/test_frost_state.py ports the C++ lambda to Python and pins the behavior with 50 tests:

firmware/tests/test_nws_parser.py ports the C++ JSON parser in the nws_poll script and pins the behavior with 15 tests:

Run with:

pytest firmware/tests/test_frost_state.py firmware/tests/test_nws_parser.py -v

The wattplot.yaml is the source of truth — if you change the C++ in the frost_tick lambda or nws_poll script, update the Python port and add a test for the new behavior.

Wiring up the canopy sensor (third DS18B20)

The 1-Wire bus on GPIO16 currently has 2 sensors (panel back, soil). To add a third:

  1. Wire the canopy probe to the same bus (parallel with the other two, single 4.7kΩ pull-up stays in place).
  2. Power up the wattplot and watch the boot log:

    [one_wire] found device 0x....
    
  3. Copy the third address into wattplot.yaml:

    - platform: dallas_temp
      one_wire_id: panel_temp_bus
      address: 0x<real_address_here>   # <-- replace placeholder
      name: "Canopy Air Temperature"
      id: canopy_temperature
      ...
    
  4. The placeholder 0x0000000000000000 will read as 127.0°C if the address is wrong — easy to spot in HA.